Inspection
Inspection Details
Equipment ID
1123
1123
Inspection Date
7/26/2017
7/26/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Joseph Jensen
Joseph Jensen
Mechanic Name
Relief Valve Pressure
410
410
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
14F 14R
14F 14R
External ID
1123
1123
Location
JCK Library
415 E, Clark St., Warrensburg, MO
Phone: (660) 543-4964
415 E, Clark St., Warrensburg, MO
Phone: (660) 543-4964
Owner
University of Central Missouri
116 S, Clark St, Warrensburg, MO 64093
116 S, Clark St, Warrensburg, MO 64093
Billing
Attn: University of Central Missouri
116 S, Clark St, , MO 64093
116 S, Clark St, , MO 64093
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency phoine not working | 11/8/2018 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certifiate in machine room | 8/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove oil recovery pump from pit and replace with a 5 gal pit can per memo-006 | 8/27/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 8/27/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire don't use elevator signage needed | 9/3/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump hole needs non combustible cover. There is a cover there but not cut out for hoses. | 11/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Scavenger pump in pit | 11/22/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | proper sump cover needs to be over hole | 11/22/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | remove scavenger pump | 11/22/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | pit sump cover needed | 7/6/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | Yes | No | Sump pump not working. 3 or 4 inches water in pit. Repair sump and remove water | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Cartop is missing cab steadiers. Replace | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Emergency battery lowering not working. Batteries | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP needed | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher out of date |