Inspection
Inspection Details
Equipment ID
19312
19312
Inspection Date
10/28/2020
10/28/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
5987720a-b160-4539-9245-9f4ab2b74a52
5987720a-b160-4539-9245-9f4ab2b74a52
Location
100 North Tucker Bldg
100 N TUCKER BLVD, SAINT LOUIS, MO
Phone: (314) 977-2966
100 N TUCKER BLVD, SAINT LOUIS, MO
Phone: (314) 977-2966
Owner
Attn: Barth Breneman
St. Louis University
3545 LINDELL BLVD 2nd Floor, SAINT LOUIS, MO 63103
Phone: (314) 977-2966
Email: barth.breneman@slu.edu
St. Louis University
3545 LINDELL BLVD 2nd Floor, SAINT LOUIS, MO 63103
Phone: (314) 977-2966
Email: barth.breneman@slu.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.11.2.1.3(w) | No | No | Replace missing bottom restrictor angles on levels 2 and 4 | 9/10/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | Yes | Replace missing cutter pins on counterweights. Ropes jumped out of grooves on counterweight sheave. | 6/4/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell does not work. | 6/4/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell do not work. | 10/28/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The car door restrictor bracket is missing on the 4th floor hoistway door and will not properly catch/restrict the opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection and repair is required. | 8/21/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Pit ladder is covered by screening making the ladder unusable. | 8/31/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator alarm bell inside the elevator is not working. Check and repair the alarm bell for proper operation and passenger safety. Reinspection required. | 8/21/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Audible alarm in car is inoperable and shall be repaired for reinspection. | 5/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) | Yes | No | Audible signal during initial recall is inoperable and shall be repaired for reinspection. | 5/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Door open button inoperable and shall be repaired for reinspection. | 8/31/2026 |