Inspection
Inspection Details
Equipment ID
22810
22810
Inspection Date
6/21/2018
6/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Shawn Estill
Shawn Estill
Relief Valve Pressure
690
690
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
99e40821-3d48-4230-a8d5-8f2ae351d166
99e40821-3d48-4230-a8d5-8f2ae351d166
Location
Manor II
518 NW SHAMROCK AVE, LEES SUMMIT, MO
518 NW SHAMROCK AVE, LEES SUMMIT, MO
Owner
John Knox Village
1001 NW CHIPMAN RD, LEES SUMMIT, MO 64081-3912
1001 NW CHIPMAN RD, LEES SUMMIT, MO 64081-3912
Billing
Attn: John Knox Village
1001 NW CHIPMAN RD, LEES SUMMIT, MO 64081-3912
1001 NW CHIPMAN RD, LEES SUMMIT, MO 64081-3912
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Please provide an MCP, or location of MCP at controller. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Please provide a Fire Service testing log, or location of testing log at controller, with monthly testing documented in log. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19.4.1 | No | No | Provide a manual shut off valve outside of hoistway for main hydraulic line. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | No | No | Provide pressure switch inline between cylinders and main valve. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.32 - Control Valve | 3.19.4.5 | No | No | Provide a pressure guage fitting and shut off outside of hoistway. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.32 - Control Valve | 3.19.4.4 | No | No | Provide manual lowering device outside of hoistway. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 3.4 | Yes | No | Minimum refuge space inadequate, note clearance on top of pump unit, with letters and numbers 2" in height, visible from landing. | 6/2/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Please provide one type ABC fire extinguisher at the 2nd landing, near elevator door. | 9/23/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Oil in pit. | 7/17/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide an MCP in machine room. | 7/17/2024 |