Inspection
Inspection Details
Equipment ID
8804
8804
Inspection Date
10/22/2020
10/22/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Jerry Reasoner
Jerry Reasoner
Relief Valve Pressure
570
570
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
6c1d5c80-f13a-484d-8ab2-b1dd5021e166
6c1d5c80-f13a-484d-8ab2-b1dd5021e166
Location
Argosy Casino
777 NW ARGOSY PKWY, RIVERSIDE, MO
Phone: (816) 746-3588
777 NW ARGOSY PKWY, RIVERSIDE, MO
Phone: (816) 746-3588
Owner
Argosy Casino
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
Billing
Attn: Argosy Casino
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
777 NW ARGOSY PKWY, RIVERSIDE, MO 64150-1512
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | repair or replace elevator phone, it rings once and then disconnects before security can answer | 11/23/2025 |
| conversion | conversion | n/a | No | No | replace the phase 1 keyswitch chicklet, the words can not be read for on, off, bypass or fire service | 11/23/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | repair the emergency phone, it has a dial tone, it dials a number, it rings once and then hangs up | 10/22/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | replace fire service phase 1 instruction chicklet, no longer able to read the markings "on, off, bypass" | 10/22/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | a new copy of the state operating certificate is to be posted in the machine room every year | 11/23/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | post a monthly fire service test log in the machine room and fill it out monthly | 11/23/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | the emergency phone rings once and then hangs up before allowing communication | 1/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate in the machine room expired 2011, update with a new copy when received from the state annually | 11/23/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Oil on pit floor, clean pit floor | 11/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Replace packing, leaking all over the pit | 11/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Fire service phase 1 keyswitch collar markings are gone, replace chicklet so markings can be read | 11/23/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | the state operating certificate in the machine room expired in 2011, update with current copy when received from the state of Missouri | 11/23/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | fire service phase 1 keyswitch collar marking are gone, replace collar so marking can be read | 11/23/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Provide updated permit in a displayable location | |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Replace illegible fire service phase 1 bezel | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Missing fire egress signage | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Owner to provide updated monthly fire service logs | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Missing fire service jewel cover on car operating panel | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil absorbent pads from the pit floor | |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Missing Fire Service Phase 1 instructions at main egress | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The state operating certificate in the machine room expired 2011, update with a new copy when received from the state annually; repeat violation 8/28/2024. Repeat violation 9/2/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire service phase 1 keyswitch collar markings are gone, replace chicklet so markings can be read; repeat violation 8/28/2024 - adding keep updated monthly Fire service log, missing cover on FS jewel on car station, missing Phase 1 instructions. Repeat violation on 9/2/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Update PM records. Repeat violation 9/2/2025 | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove oil absorbent pads from pit floor | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Missing Fire egress signage at main floor. Repeat violation 9/2/2025 |