Inspection
Inspection Details
Equipment ID
22085
22085
Inspection Date
11/5/2020
11/5/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Keith Tynes, Jr
Keith Tynes, Jr
Relief Valve Pressure
950
950
Slide
Instantaneous
Instantaneous
Governor Rope Pull
NA
NA
Door Closing Force
24
24
External ID
79260332-c8a1-4eac-8efb-bf9dc35b6b14
79260332-c8a1-4eac-8efb-bf9dc35b6b14
Location
Kennard CJA
5031 POTOMAC ST, SAINT LOUIS, MO
Phone: (314) 633-9103
5031 POTOMAC ST, SAINT LOUIS, MO
Phone: (314) 633-9103
Owner
Attn: UNK
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: Rosmon.Johnson@slps.org
St.Louis Board of Education
801 N 11TH ST, SAINT LOUIS, MO 63101
Phone: (000) 000-0000
Email: Rosmon.Johnson@slps.org
Billing
Attn: Sandy Russell
Century Elevator
P.O. Box 510571, St. Louis, MO 63151
Phone: (314) 846-3500
Email: sandy@centuryelevatorservice.com
Century Elevator
P.O. Box 510571, St. Louis, MO 63151
Phone: (314) 846-3500
Email: sandy@centuryelevatorservice.com
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.26 - Broken rope, chain, or tape switch | 8.11.2.1.3(i) | x | x | Replace slack chain switch. Switch has been wet and is corroded. | 8/27/2019 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | Pit equipment is rusted. Correct source of water backup. | 10/17/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions | 8.11.3.4.1 | x | A category 5 full load test is required in 2019. | 11/5/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.13.5 | x | x | The door open button shall be operational on fire service | 11/5/2020 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Phase 1 & Phase 2 fire service key switches shall be keyed the same. | 11/5/2020 |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | x | The keys were not on-site. Could not check COP stop switch or phase 2 fire service. | 11/5/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.1 - Door Re-opening device | 8.6.4.13.1(c) Door Reopening Devices | Car door open button shall be operational. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | Phase 1 fire recall shall be operational. (Violation corrected 12/3/2020) Re-Inspection Pending | 3/15/2022 |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.1 - Door Re-opening device | 8.6.4.13.1(c) Door Reopening Devices | Car door open button shall operate | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 | x | Keys to operate unit shall be available, unable to verify Phase II, no keys. Re-inspection required | 1/26/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A written MCP shall be kept in the machine room for each unit | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Unable to test safeties due to no documentation. Re-inspection required | 1/26/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.1 - Door Re-opening device | 8.6.4.13.1(c) Door Reopening Devices | Provide car door open button to work. (Pushing floor number opens door). | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | x | Provide existing emergency lights and bell to work. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Provide existing battery backup lowering unit to work. | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Bottom floor hoist way door missing roller, provide. | |||
A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | OSV in the pit is unsealed, provide testing. |