Inspection
Inspection Details
Equipment ID
11171
11171
Inspection Date
11/6/2020
11/6/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
d7132016-6a35-4045-9b30-5540d08b0edb
d7132016-6a35-4045-9b30-5540d08b0edb
Location
Pierre Laclede Center
7733 FORSYTH BLVD, CLAYTON, MO
Phone: (314) 862-2432
7733 FORSYTH BLVD, CLAYTON, MO
Phone: (314) 862-2432
Owner
Attn: LCP Forsyth Blvd Prop. Owner, LLC
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, CLAYTON, MO 63105
Phone: (314) 862-2432
Email: d_kasten@commonwealth.com
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, CLAYTON, MO 63105
Phone: (314) 862-2432
Email: d_kasten@commonwealth.com
Billing
Attn: LCP Forsyth Blvd Prop. Owner, LLC
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: dkasten@commonwealthcommercial.com
LCP Forsyth Blvd Prop. Owner, LLC
7733 Forsyth Blvd. Bldg Code: 251902, SAINT LOUIS, MO 63105
Phone: (000) 000-0000
Email: dkasten@commonwealthcommercial.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Car emergency telephone is not loud enough to make two way communication possible. | 4/18/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Schedule a full lad test of the emergency power system on elevators 1-8. | 4/18/2019 |
| conversion | conversion | n/a | No | No | Car emergency lighting shall work. | 10/1/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Shorten the hoist ropes for proper up final limit switch operation. | 4/18/2019 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Test emergency power. | 7/28/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 11/6/2020 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1001.2(a)(17) | Yes | No | Emergency/standby power operation of the elevators shall be operational. | 10/5/2021 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/26/2022 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 4/26/2022 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Car door restrictor shall work at all floors. | 6/26/2023 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/26/2023 |
| A17.1-1996 : Elevators | 3.9 - Floor and emergency identification numbering | 211.9 | No | No | COP shall display unit identifier (Elevator #8). | 3/26/2024 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | No | No | Pit shall be kept clean. Remove excess debris. | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Phase 2 switch Halo and Call Cancel Halo to be replaced. It is faded and unreadable. | 3/26/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 7/18/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired State operating certificate in the machine room. | 4/24/2026 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell not working. | 4/24/2026 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired State operating certificate in the machine room. |