Inspection
Inspection Details
Equipment ID
6904
6904
Inspection Date
11/13/2020
11/13/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
16
16
External ID
bbce57a0-b729-469c-9059-aad12411992d
bbce57a0-b729-469c-9059-aad12411992d
Location
AT & T- Olive Street
2651 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 658-5381
2651 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 658-5381
Owner
Attn: Bill Monchan
AT & T- Olive Street
2651 OLIVE ST RM 135, SAINT LOUIS, MO 63103
Phone: (314) 658-5381
AT & T- Olive Street
2651 OLIVE ST RM 135, SAINT LOUIS, MO 63103
Phone: (314) 658-5381
Billing
Attn: Bill Monchan
AT & T
2651 Olive St, St. Louis, MO 63103
Phone: (314) 658-5381
AT & T
2651 Olive St, St. Louis, MO 63103
Phone: (314) 658-5381
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (J) - Counterweights | (J)1 | No | No | Negative counterweight runby, remove counterweight blocking. | 9/22/2025 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | Restore door operation and re-test fire service. | 11/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | 7th floor push button needs to be replaced. | 9/22/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)3 | No | No | Compensating chains need to be shortened. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair inoperative emergency lights. | 11/19/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Category 5 weight testing has not been performed since 2016. Category 5 testing shall be performed and witnessed immediately. | 9/22/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. Mechanic stated the lock jams from the inside. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Machinery, controllers, governors, disconnects shall be numbered conspicuously. Governors are not numbered. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Suspension means shall have proper data tags. | 9/22/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 9/22/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. | 12/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Multi-year violation. | 12/18/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Fire service shall be tested and documented monthly. | 12/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. (2nd Notice) | 12/18/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency lighting appears to have been removed, shall be reinstalled and tested. Violations listing indicated unit had EM Lighting but does not appear to be present currently. 3rd NOTICE. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant MCP and related on-site documentation shall be provided in the machine room. Violation: no required documents onsite.3rd NOTICE | |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | No Fire Service Testing Logs, tested month. 2nd NOTICE. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | 0 A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3rd NOTICE. | |
| A17.1-2016 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 | Yes | No | 2nd floor hoistway door is missing an upthrust roller bearing. |