Inspection
Inspection Details
Equipment ID
10730
10730
Inspection Date
11/10/2020
11/10/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
John Harvey
John Harvey
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
a11e4670-d384-4c33-a3a6-445eb375b7ff
a11e4670-d384-4c33-a3a6-445eb375b7ff
Location
Barbara Jordan Elementary School
1500 82ND BLVD, SAINT LOUIS, MO
Phone: (314) 993-4282
1500 82ND BLVD, SAINT LOUIS, MO
Phone: (314) 993-4282
Owner
University City School District
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
Billing
Attn: University City School District
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
8136 GROBY RD, UNIVERSITY CITY, MO 63130-2042
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post the current state operating certificate in the elevator machine room. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide code compliant MCP. Documents on site not complete. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals | Yes | No | During the relief valve test, the packing on one of the jacks failed. Replace packing and re-test. Unit shut down for repairs. | 11/1/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The inspection is incomplete. The following items still need to be tested: Door pressure, fire service, emergency light, emergency bell, and emergency phone. | 11/1/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | No | No | Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. | 2/13/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 2.26.4 | Yes | No | Feeder locations for the main and lighting branch circuits shall be marked on the disconnects. | 11/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Two-way communication device shall work and give location. | 11/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 11/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire service shall be tested and documented monthly. | 11/18/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/18/2025 |