Inspection
Inspection Details
Equipment ID
11222
11222
Inspection Date
5/30/2018
5/30/2018
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Larry Bullard
Larry Bullard
Relief Valve Pressure
Slide
26"
26"
Governor Rope Pull
600
600
Door Closing Force
26
26
External ID
eb0f689b-efb0-46d5-8186-81d9a32bf4c5
eb0f689b-efb0-46d5-8186-81d9a32bf4c5
Location
Jackson County Courthouse
415 E 12TH ST, KANSAS CITY, MO
415 E 12TH ST, KANSAS CITY, MO
Owner
Jackson Co Courthouse Facilities Mgmt
415 E 12TH ST, KANSAS CITY, MO 64106-2706
415 E 12TH ST, KANSAS CITY, MO 64106-2706
Billing
Attn: Jackson Co Courthouse Facilities Mgmt
415 E 12TH ST STE 6M, KANSAS CITY, MO 64106-2706
415 E 12TH ST STE 6M, KANSAS CITY, MO 64106-2706
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Main hoisting ropes undersized. Min.469 actual .460 | 4/9/2019 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency lights not working. | 6/29/2021 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency alarm not working. | 6/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | All landing doors need maintenance, and adjustments. Rollers, upthrusts, eccentrics, etc. | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | Supply test of fire alarm devices | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | Yes | No | seal voids and penetrations in hoistway | 6/29/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 8/30/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | Yes | No | Provide an audible signal while in recall. | 5/19/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | Provide an audible signal during recall. | 5/22/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair the pit lighting. | 5/22/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. |