A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12) -
|
|
|
A completed fire service testing log shall be kept on-site.
|
11/26/2019
|
A17.1-1996 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
1001.2(d)(12) -
|
|
|
Phase 2 fire service operating instructions in the car are worn and unreadable and shall be replaced.
|
11/26/2019
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
1001.2(a)(16)
|
|
|
The capacity plate in the car is worn and unreadable and shall be replaced.
|
11/26/2019
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display the current state operating certificate.
|
11/26/2019
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022)
|
11/27/2021
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO state operating certificate shall be displayed in the elevator machine room.
|
11/27/2021
|
A17.1-1996 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
11/27/2021
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit has an excessive amount of water in it. Take corrective action as needed.
|
11/22/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
The auxiliary power lowering operation shall be functional.
|
5/30/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The fire service phase one key-switch bezel shall be legible.
|
11/12/2024
|
A17.1-1996 : Elevators
|
1.16 - Rated load, platform area, and data plate
|
207
|
|
|
A capacity plate listing the capacity in pounds and prominently displayed in the car enclosure.
|
11/12/2024
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
101.5a Lighting
|
|
|
The machine room light fixture shall be properly fastened to the ceiling in a permanent fashion.
|
11/12/2024
|