Inspection
Inspection Details
Equipment ID
20415
20415
Inspection Date
11/17/2020
11/17/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
220/430
220/430
Slide
Governor Rope Pull
Door Closing Force
F-22 R-24
F-22 R-24
External ID
e3b010fc-5e07-4f12-ad3e-10579cbe4bc1
e3b010fc-5e07-4f12-ad3e-10579cbe4bc1
Location
Harris Stowe University- New Residence Hall
3026 LACLEDE AVE, SAINT LOUIS, MO
Phone: (314) 647-3535
3026 LACLEDE AVE, SAINT LOUIS, MO
Phone: (314) 647-3535
Owner
Attn: Harris-Stowe State University
Harris-Stowe State University
3026 LACLEDE AVE, SAINT LOUIS, MO 63103
Phone: (314) 340-3306
Email: Gatess@HSSU.EDU
Harris-Stowe State University
3026 LACLEDE AVE, SAINT LOUIS, MO 63103
Phone: (314) 340-3306
Email: Gatess@HSSU.EDU
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Existing cab emergency telephone doe not work and shall be repaired and tested. | 7/20/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | The pit shall be kept clean. | 7/7/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 7/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 5/26/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 2.7.5.2 | No | No | Upon arrival, machine room and tank are open with fan blowing to keep both cool. The motor controller shall be located in a machine space that is provided with natural or mechanical means to keep the ambient air temperature and humidity in the range specified by the elevator equipment manufacturer to ensure safe and normal operation of the elevator. | 7/12/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.11.3.2.2 Cylinders | Yes | Yes | Elevator failed 15 minute static leak down test. Must be repaired and re-inspected before returning to public use. Elevator Red Tagged. | 6/28/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.31 - Relief Valves | 3.19.4.2 (Pump Relief Valve) | No | No | Relief valve adjuster shall be sealed. | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | The machine room door shall be self-closing, self-locking, and operable from the interior space without the use of a key. Door is currently propped open with a fan. | 11/24/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | No | No | Adjust up-thrust roller bearings for proper clearance to door hanger track. (Multiple floors) | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7.1.2 Minimum Illumination | No | No | Repair the cab lighting so all lamps are operational. | 11/24/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | NO MO State operating certificate in the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | Non-elevator materials need to be removed from the machine room. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | Top of car needs to be cleaned. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit needst o be cleaned. |