Inspection
Inspection Details
Equipment ID
12770
12770
Inspection Date
11/20/2020
11/20/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
410
410
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
5f4ed3e3-7e13-410d-b2a0-3abd3130405e
5f4ed3e3-7e13-410d-b2a0-3abd3130405e
Location
McCormack House
4575 CADET AVE, SAINT LOUIS, MO
Phone: (314) 371-2525
4575 CADET AVE, SAINT LOUIS, MO
Phone: (314) 371-2525
Owner
Attn: McCormack House
McCormack House
4575 CADET AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
McCormack House
4575 CADET AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Billing
Attn: McCormack House
McCormack House
4575 CADET AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Email: Brionna.Ivie@McCormackBaron.com
McCormack House
4575 CADET AVE, SAINT LOUIS, MO 63110
Phone: (000) 000-0000
Email: Brionna.Ivie@McCormackBaron.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.4 - Machine space | 100.3d | No | No | Remove non-electrical material from machine space. | 9/19/2019 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV not sealed or tagged, notified on last visit, needs to be sealed & tagged within 90 days | 8/23/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove debris in pit | 5/27/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light in-operable | 5/27/2022 |
| A17.1-2016 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(2) Hydraulic elevator, dumbwaiter, or material lift Placed out of Service | Yes | Yes | Elevator leaked down 2" in 15 minutes. Placed out of service until repairs can be made. | 8/23/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | MCP records should be kept on site for each elevator | 5/27/2022 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | Phase II keyswitch is in-operable | 8/23/2022 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 6/14/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Debris in pit | 8/4/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light inoperable | 8/4/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Reinspection of elevator phone. Still not working. repair phone. | 7/13/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Reinspection of debris in elelvator pit. Still dirty. Clean elelvator pit. | 8/15/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Reinspection of elelvator pit lights. STill not working. Repair pit lights. | 8/15/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Re-inspection of elevator phone, still not working, needs repaired. Re-inspection required | 7/31/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Re-inspection of elevator pit lights, still not working. Need to repair lights. Re-inspection required | 7/31/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Re-inspection of elevator phone, still not working. Needs repaired. Re-inspection required | 8/15/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Debris in pit. | 9/8/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | Pit light inoperable. | 9/8/2023 |
| A17.1-1996 : Elevators | 2.32 - Control Valve | 303 | No | No | During The 15 Minute Holding procedure, the Elevator Technician determined oil leaking back into the tank. Repair or replace as needed. | 11/18/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Emergency battery lowering device does not work, needs repaired. Re-inspection required |