Inspection
Inspection Details
Equipment ID
25112
25112
Inspection Date
11/23/2020
11/23/2020
Inspection Type
New Installation
New Installation
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Shane Warth
Shane Warth
Relief Valve Pressure
Slide
2"
2"
Governor Rope Pull
25/195
25/195
Door Closing Force
22
22
External ID
7e169531-6624-45f9-b72c-90bf3ca21853
7e169531-6624-45f9-b72c-90bf3ca21853
Location
Chroma II
900 S Sarah St, St. Louis, MO
Phone: (000) 000-0000
Email: kelly.bigshy@kone.com
900 S Sarah St, St. Louis, MO
Phone: (000) 000-0000
Email: kelly.bigshy@kone.com
Owner
Attn: Green Street
Green Street Building Group
8451 Maryland Ave, Clayton, MO 63105
Phone: (000) 000-0000
Email: kelly.bigshy@kone.com
Green Street Building Group
8451 Maryland Ave, Clayton, MO 63105
Phone: (000) 000-0000
Email: kelly.bigshy@kone.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) | Yes | No | The in car emergency telephone shall be operational. | 11/25/2020 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.10.2.2.3(r) | Yes | No | Install hoistway and car top duct covers. | 11/25/2020 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | Yes | No | The electrical disconnects shall be labeled with the location, name, and breaker numbers of the panel from which it is fed. | 11/25/2020 |
| A17.1-2016 : Elevators | 3.20 - Governor rope | 2.18.5 | Yes | No | Governor rope shall not rub guard. | 11/25/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | Yes | No | Provide code compliant onsite documents. | 11/25/2020 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | Provide a code compliant fire extinguisher near the machine space. | 11/25/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3 | Yes | Yes | Test Phases 1 & 2 fire service and all fire service initiating devices. | 11/25/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.9 Elevator Corridor Call Station Pictograph | Yes | No | Provide "In Case of Fire" signage. | 11/25/2020 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.11.10.1 | Yes | No | 2.11.10.1.1 - Provide landing sill guards. | 11/25/2020 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.10.2.2.2(ll) | Yes | No | 8.10.1.1.4 - Provide acceptance test tags. | 11/25/2020 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Battery lowering shall be operational. | 11/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The suspension rope retainer on the drive sheave is rubbing the hoist ropes. Adjust for proper clearance. | |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |