Inspection
Inspection Details
Equipment ID
10060
10060
Inspection Date
12/10/2020
12/10/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
30+
30+
External ID
355f6810-c32b-4a09-8db5-31268061ddf7
355f6810-c32b-4a09-8db5-31268061ddf7
Location
AT & T- Washington
3810 WASHINGTON BLVD, SAINT LOUIS, MO
Phone: (314) 781-1980
3810 WASHINGTON BLVD, SAINT LOUIS, MO
Phone: (314) 781-1980
Owner
Attn: Dale Hughes
AT&T
3810 Washington Blvd, St. Louis, MO 63108
Phone: (314) 602-5453
Email: hd652p@att.com
AT&T
3810 Washington Blvd, St. Louis, MO 63108
Phone: (314) 602-5453
Email: hd652p@att.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace or reinforce catwalk in pit | 2/20/2019 |
| conversion | conversion | n/a | No | No | No fire extinguisher in machine room | 2/20/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Adjust car door close pressure to under 30lb. | 11/16/2018 |
| conversion | conversion | n/a | No | No | Handi-box cover on cart top is missing | 2/20/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | No | No | The elevator car door closing force is over the maximum allowable force of 30lbs. Readjust door closing force to be less than 30lbs. Reinspection required. | 3/26/2024 |
| A17.1-2016 : Elevators | 3.28 - Counterweight and counterweight buffer | 8.11.2.1.3(m) | No | No | The bottom guide rollers on the counterweight are cracked and shall be replaced. | 3/26/2024 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 8.11.2.1.3(r) | No | No | A receptacle box is missing its cover plate on top of the car exposing electrical connections. The cover plate shall be reinstalled to limit accidental contact by maintenance and emergency personnel. | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Counterweight guide rollers are deteriorated and causes unsafe condition. Re-inspection required | 3/26/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Car door closing force is way above 30 lbs and shall be adjusted to 30 lbs or below. Re-inspection required | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Counterweight rollers are deteriorating and shall be replaced. Re-inspection required | 3/26/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Car door force exceeds code, adjust as needed. | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Top and bottom counterweight roller guides worn, replace as needed. | 12/11/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Car top electric junction box missing cover. | 12/11/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | 3/26/2024 |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator emergency power selector switch (lobby). | 3/26/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean the car top. | 12/11/2025 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | Phase I recall not working, car removed from service. | 3/26/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)7 | Yes | No | Door force exceeds code. | 1/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Yes | No | Bottom c/w roller guides bad, replace. | 1/7/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | Car top electric j/b missing cover. | 1/7/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made operational. Re-inspection required |