Inspection
Inspection Details
Equipment ID
13945
13945
Inspection Date
4/10/2018
4/10/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
James Mueller
James Mueller
Mechanic Name
Kenneth Gustavson
Kenneth Gustavson
Relief Valve Pressure
Slide
N/A
N/A
Governor Rope Pull
N/A
N/A
Door Closing Force
30
30
External ID
522a7006-0a62-4d27-b3c5-d5dbe1868700
522a7006-0a62-4d27-b3c5-d5dbe1868700
Location
U-Haul Center of Kingshighway
1641 S KINGSHIGHWAY BLVD, SAINT LOUIS, MO
1641 S KINGSHIGHWAY BLVD, SAINT LOUIS, MO
Owner
U-Haul International
PO BOX 21502, PHOENIX, AZ 85036-1502
PO BOX 21502, PHOENIX, AZ 85036-1502
Billing
Attn: U-Haul Company of St. Louis
418 S TUCKER BLVD, SAINT LOUIS, MO 63102-1104
418 S TUCKER BLVD, SAINT LOUIS, MO 63102-1104
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - red tag | Yes | Yes | The doors will not open at the recall floor on Phase 1 fire recall. Unit Red-Tagged. | 8/23/2018 |
| conversion | conversion | n/a | No | No | Walk in pit door shall be self-closing and self-locking. | 10/1/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Car door pressure exceeds the 30 lbs limit. | 8/23/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Walk in pit door shall be self-closing and self-locking. - Reinspection Required | 10/1/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A code compliant maintenance control program (MCP) shall be available and the documentation required to be kept on site, shall be located in the machine room. | 10/7/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | A junction box for one of the machine room light fixtures is missing a cover. | 10/7/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | Yes | The smoke detectors in the elevator lobbies shall be connected to the elevators and tested for proper operation. Unit left in service and local fire department notified of the situation. Violation corrected 9/28/2020 and scheduled for re-inspection on 10/9/2020. | 10/9/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 11/3/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 11/3/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide a code compliant MCP including onsite documents. No maintenance charts. No monthly Fire Service checklist. No repair or test logs. |