Inspection
Inspection Details
Equipment ID
8598
8598
Inspection Date
12/8/2020
12/8/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
b5b7d263-4ace-421e-98f6-f07189234d76
b5b7d263-4ace-421e-98f6-f07189234d76
Location
Veronica House
12284 De Paul Dr, Bridgeton, MO
Phone: (314) 591-1660
12284 De Paul Dr, Bridgeton, MO
Phone: (314) 591-1660
Owner
Attn: The Sarah Community
The Sarah Community
12284 DE PAUL DR, BRIDGETON, MO 63044
Phone: (000) 000-0000
The Sarah Community
12284 DE PAUL DR, BRIDGETON, MO 63044
Phone: (000) 000-0000
Billing
Attn: The Sarah Community
The Sarah Community
12284 DE PAUL DR, BRIDGETON, MO 63044
Phone: (000) 000-0000
Email: rgibbons@thesarahcommunity.org
The Sarah Community
12284 DE PAUL DR, BRIDGETON, MO 63044
Phone: (000) 000-0000
Email: rgibbons@thesarahcommunity.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Need copy of current state operating certificate in machine room. | 10/4/2018 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | A completed fire service testing log shall be kept on-site. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Provide car numbering on the controller. | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | Provide car numbering on disconnect(s). | 10/9/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 8.11.2.1.3(o) | No | No | Provide car numbering on car top. | 10/9/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 10/9/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | 8.6.1.7.5 - The emergency lowering device (ERU) shall be operational. | 10/9/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 8.6.4.19.7 - Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. | 11/4/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | 8.6.4.19.7 - Operation of elevators equipped with standby or emergency power shall be tested to determine conformance with the applicable requirements. Tests shall be performed with no load in the car. | 12/8/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 12/28/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is not tagged or sealed. Category 5 testing is overdue. Unit to be red tagged if not completed within 90 days. | 9/9/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power must be tested annually. (2nd Notice) | 9/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The MCP is missing. | 10/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit must be clean and free of oil and debris. | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | The overspeed valve is not tagged or sealed. Category 5 testing is overdue. Unit to be red tagged if not completed within 90 days. | 10/14/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | Battery lowering function shall be operational. Repair and test or apply for State variance. | 6/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator, annually. Last tested 9/9/24. | 6/22/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | Yes | No | There is a sprinkler riser that runs the full length of the hoistway. Take corrective action as needed or apply for a variance. | 6/22/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator, annually | |
| MO Minimum : Elevators | (A) - Hoistways | (A)17 | Yes | No | There is a sprinkler riser that runs the full length of the hoistway. Take corrective action as needed or apply for a variance. |