Inspection
Inspection Details
Equipment ID
17437
17437
Inspection Date
12/11/2020
12/11/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Charles Brinkman
Charles Brinkman
Mechanic Name
Matthew Martin
Matthew Martin
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
57c942a3-32fd-4e1b-950b-9572acf01d3c
57c942a3-32fd-4e1b-950b-9572acf01d3c
Location
Hillsboro Elementary
13 Hawk Dr, Hillsboro, MO
Phone: (636) 789-3966
13 Hawk Dr, Hillsboro, MO
Phone: (636) 789-3966
Owner
Attn: Hillsboro R-3 School District
Hillsboro R-3 School District
20 HAWK DR, HILLSBORO, MO 63050-5080
Hillsboro R-3 School District
20 HAWK DR, HILLSBORO, MO 63050-5080
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | No | No | 1) Only machinery and equipment used in conjunction with the function or use of the elevator shall be permitted in the elevator machine room. Plumbing lines, water and drain lines, coming through floor from a renovation to the building must be removed or apply for a variance. | 2/7/2020 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | 2) Machine rooms and machinery spaces shall be enclosed throughout their height with fire-resistive enclosures as required by the building code. Openings created by the installation of plumbing lines from the renovation of the building have violated the fire rating. | 2/7/2020 |
| A17.1-1996 : Elevators | 3.3 - Top-of-car operating device | 210.1d | No | No | 3) Operating devices for inspection operation shall be provided on the top of the car. The top of car station for inspection operation, up and down, is not functioning. | 2/7/2020 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | No | No | 1) Only machinery and equipment used in conjunction with the function or use of the elevator shall be permitted in the elevator machine room. Plumbing lines, water and drain lines, coming through floor from a renovation to the building must be enclosed or guarded so that any leaks that occur will not effect elevator equipment. As per the Elevator Safety Board, sent in a letter. | 2/7/2020 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | 2) Machine rooms and machinery spaces shall be enclosed throughout their height with fire-resistive enclosures as required by the building code. Openings created by the installation of plumbing lines from the renovation of the building have violated the fire rating. | 2/7/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | 1) A record that shall include the maintenance tasks listed with the associated requirements of Section 8.6 identified in the Maintenance Control Program. Ref: 8.6.1.4.1(a)(1) | 2/11/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.2 Callbacks (Trouble Calls) Documentation | No | No | 2) A record of callbacks shall be maintained and shall include the description of reported trouble, dates, time, and corrective action(s) taken that are reported by any means to elevator personnel. Ref: 8.6.1.4.2 | 2/11/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | 3) All electrical wiring in the hoistway shall be enclosed or be in compliance with NFPA 70, top floor interlock cover missing. NEC 620.4 Ref: (A) 16 | 2/11/2021 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | 4) Overspeed valves, where provided, shall be inspected and tested to verify that they will stop the car, traveling down with rated load. No seal on valve. Ref: 8.6.5.16.5 Note: This Shall Be Done Next Year, during the annual inspection. | 2/11/2021 |