Inspection
Inspection Details
Equipment ID
6174
6174
Inspection Date
12/2/2020
12/2/2020
Inspection Type
Reinspection
Reinspection
Inspector Name
Gregory Sacks
Gregory Sacks
Mechanic Name
Dustin Schmidt
Dustin Schmidt
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
9c522c29-d75a-4b1c-bdb2-7235f3d2c483
9c522c29-d75a-4b1c-bdb2-7235f3d2c483
Location
Hoctor Building
1016 W COLUMBIA ST, FARMINGTON, MO
Phone: (573) 631-1222
1016 W COLUMBIA ST, FARMINGTON, MO
Phone: (573) 631-1222
Owner
SORTS
1016 W COLUMBIA ST, FARMINGTON, MO 63640-2902
1016 W COLUMBIA ST, FARMINGTON, MO 63640-2902
Billing
Attn: OA Facilities Mgt.-Interagency
301 W HIGH ST RM 780, JEFFERSON CITY, MO 65101-1517
301 W HIGH ST RM 780, JEFFERSON CITY, MO 65101-1517
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.3.5 | Yes | No | An emergency power test with 125% capacity shall be performed and witnessed. | 12/2/2020 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Provide testing of Phase I operations, record results. | 7/12/2023 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | Provide testing of Phase II operations, record results. | 7/12/2023 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Check door force. | 7/12/2023 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.6.4.20.1 | Yes | No | Provide Cat 1 testing of car safeties, check slide..Car stopped running. | 7/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work on backup power and be answered 24/7. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Top final limit switch was not actuated before counterweights compressed buffer. Red-tagged, Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | Yes | Bottom final limit switch activates just as car compresses buffer. Red-tagged, Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car shall work for more than 3 seconds. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection incomplete, elevator ceased operation during testing. Need to perform the following tests to complete inspection: all fire service, pit equipment and get slide measurement. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency light in car shall work for more than 3 seconds. Re-inspection required | 10/7/2025 |