Inspection
Inspection Details
Equipment ID
7124
7124
Inspection Date
12/8/2020
12/8/2020
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
Don McFadden, Jr.
Don McFadden, Jr.
Relief Valve Pressure
Slide
21"
21"
Governor Rope Pull
90/600
90/600
Door Closing Force
18
18
External ID
1f844230-a1bd-4806-90f2-ce5469d9f110
1f844230-a1bd-4806-90f2-ce5469d9f110
Location
Gallery 515
515 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 241-5964
515 OLIVE ST, SAINT LOUIS, MO
Phone: (314) 241-5964
Owner
Attn: Brandonview LLC
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: mgummels@stlluxury.com
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: mgummels@stlluxury.com
Billing
Attn: Brandonview LLC
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: gallery515@stlluxury.com
Brandonview LLC
515 Olive St, Ste 106, St. Louis, MO 63101
Phone: (314) 421-4500
Alt Phone: (314) 328-7900
Email: gallery515@stlluxury.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | Provide a current inspected fire extinguisher in the machine room. | 2/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Provide code compliant machine room lighting. | 2/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.6 - Ventilation | 8.11.2.1.2(f) | No | No | Make machine room exhaust fans code compliant. | 2/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide code compliant pit lighting. | 2/4/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/15/2022 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 2.11.10.2 | No | No | Illumination at Landing Sills: The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10 fc. Note: Some lobbies are under construction, and not lighted. | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.10 - Numbering of elevators, machines, and disconnect switches | 8.11.2.1.2(j) | No | No | The buffers, pit channels, and/or the compensating sheave assembly, which are visible from the pit access door, shall be marked with the car identification number with a minimum of 2 inches in height and of a contrasting color to its background. | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 3/15/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.1 | No | No | The identification number for each elevator shall be painted on, engraved, or securely attached adjacent to or on every elevator entrance at the designated level, and shall be a minimum of 3 inches in height. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean and dry. | 7/8/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Missing 2022 & 2023 and fire service logs and PM/repair logs. | 7/8/2025 |