Inspection
Inspection Details
Equipment ID
6578
6578
Inspection Date
12/16/2020
12/16/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Vernon Livergood
Vernon Livergood
Mechanic Name
Relief Valve Pressure
563
563
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
bfb3bf12-e1dd-4145-b18a-e384c140473d
bfb3bf12-e1dd-4145-b18a-e384c140473d
Location
Best Western Airport Inn & Suites
2512 NW PRAIRIE VIEW RD, PLATTE CITY, MO
Phone: (816) 858-0200
2512 NW PRAIRIE VIEW RD, PLATTE CITY, MO
Phone: (816) 858-0200
Owner
Attn: Ramada
Ramada
2512 NW PRAIRIE VIEW RD, PLATTE CITY, MO 64079
Phone: (816) 858-0200
Email: ramadaplatecity@gmail.com
Ramada
2512 NW PRAIRIE VIEW RD, PLATTE CITY, MO 64079
Phone: (816) 858-0200
Email: ramadaplatecity@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | phase one fire serv. buzzer not working | 12/27/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Non elev. related materials stored in machine room. | 12/27/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | no current operatig cirtf. displayed | 12/27/2018 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | No audible signal during fire recall | 6/19/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Perform overspeed valve test with inspector present | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Written checkout procedure shall be kept permanently on site | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove non-elevator related material from the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Test and log firefighter operation monthly | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current state operating certificate inside the machine room | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking and non-defeatable | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door shall be self-locking and non-defeatable | |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | No | No | No audible signal (buzzer) during fire recall | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Non defeatable lock on machine room door remains from 2023 installed a deadbolt lock | 1/24/2024 |