Inspection
Inspection Details
Equipment ID
15024
15024
Inspection Date
6/18/2018
6/18/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Richard Dalman
Richard Dalman
Relief Valve Pressure
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
28
28
External ID
57aa2c6a-16be-4016-b5cd-5cf845260883
57aa2c6a-16be-4016-b5cd-5cf845260883
Location
Mosaic Life Care
5325 FARAON ST, SAINT JOSEPH, MO
5325 FARAON ST, SAINT JOSEPH, MO
Owner
St. Joseph Downtown Development LLC
5325 FARAON ST, SAINT JOSEPH, MO 64506-3488
5325 FARAON ST, SAINT JOSEPH, MO 64506-3488
Billing
Attn: St. Joseph Downtown Development LLC
5325 FARAON ST, SAINT JOSEPH, MO 64506-3488
5325 FARAON ST, SAINT JOSEPH, MO 64506-3488
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Test and log firefighter operation monthly | 11/17/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(b)(4) | No | No | Post emergency evacuation of passengers procedure inside machine room | 11/17/2020 |
| A17.1-1996 : Elevators | 1.8 - Door closing force | 1001.2(a)(8) | Yes | No | Door pressure exceeds 30# | 12/8/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Emergency light does not operate | 12/8/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not operate | 12/8/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Install FEO-K1 keyswitches. All elevators in the same building shall have firefighter keyswitches operated by the same key | 10/24/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test operation of elevator on emergency power with an inspector present | 12/8/2021 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.2-211.8 | Yes | Yes | In car firefighter keyswitch does not disable car calls or door close operation when keyed to the HOLD position | 11/29/2022 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Door force exceeds 30# | 11/29/2022 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test operation of elevator on emergency power | 11/29/2022 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4.1(a)(1) | No | No | MRL not up to date | 2/1/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 2/1/2024 |
| A17.1-2016 : Elevators | 1.8 - Door closing force | 8.6.4.19.8 | Yes | No | Door force exceeds 30# | 10/24/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Test emergency power operation | 12/13/2023 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate not displayed | 1/5/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | The emergency power was not tested. | 11/13/2024 |