Inspection
Inspection Details
Equipment ID
12588
12588
Inspection Date
6/8/2020
6/8/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
22
22
External ID
bbe03bfa-dc4a-4a16-a01c-ad282dae8a1d
bbe03bfa-dc4a-4a16-a01c-ad282dae8a1d
Location
West County Center
44 W COUNTY CTR, DES PERES, MO
Phone: (314) 288-2020
44 W COUNTY CTR, DES PERES, MO
Phone: (314) 288-2020
Owner
Attn: Andrew Goldacker
CBL Properties/West County center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
CBL Properties/West County center
80 W County Center, Des Peres, MO 63131
Phone: (314) 288-2026
Alt Phone: (314) 409-8204
Email: andrew.goldacker@cblproperties.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Post Mo State certificate in machine room | 11/4/2019 |
| conversion | conversion | n/a | No | No | Door restrictor must be operational | 11/4/2019 |
| conversion | conversion | n/a | No | No | Pit needs cleaning | 11/4/2019 |
| conversion | conversion | n/a | No | No | Alarm bell not working | 11/4/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 11/4/2019 |
| A17.1-1996 : Elevators | 1.2 - Stop switches | 1001.2(a)(2) | No | No | Stop switch alarm bell must work. | 11/4/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm bell must work. | 7/9/2019 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | Emergency light must work. | 11/4/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Light needs to work in the pit. | 7/9/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Red Tag) | Yes | Yes | Alarm bell not working. | 10/11/2019 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light not working. | 10/11/2019 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current certificate in machine room. | 11/4/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Clean oil and debris from elevator pit. | 1/4/2021 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean elevator car top. | 1/4/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform test on or before next annual inspection. | 4/27/2022 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit bucket is overflowing. Clean pit and replace cylinder gland packing. | 8/2/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm is not working. Re-inspection required | 4/17/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, have serviced or replaced | 3/13/2026 |