Inspection
Inspection Details
Equipment ID
5793
5793
Inspection Date
6/20/2018
6/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
David Folkert
David Folkert
Mechanic Name
Jasen Kennedy
Jasen Kennedy
Relief Valve Pressure
400
400
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
dd236c06-6571-477f-81e7-8207cc2a399e
dd236c06-6571-477f-81e7-8207cc2a399e
Location
Boder Building
105 S 4TH ST, SAINT JOSEPH, MO
105 S 4TH ST, SAINT JOSEPH, MO
Owner
JaJo Investment LLC
520 N BELT HWY, SAINT JOSEPH, MO 64506-3008
520 N BELT HWY, SAINT JOSEPH, MO 64506-3008
Billing
Attn: JaJo Investment LLC
520 N BELT HWY, SAINT JOSEPH, MO 64506-3008
520 N BELT HWY, SAINT JOSEPH, MO 64506-3008
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Pit can is overflowing. Pit can shall not be permitted to overflow. | 6/15/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove hydraulic oil from pit floor. Pit floors shall be kept clean and dry. | 6/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide written documentation inside machine room of quantity of hydraulic fluid added to system and emptied from pit can. | 6/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance Control Plan records for the elevator need to be viewable on site. | 6/15/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | No maintenance control plan | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | No maintenance records on site | 10/28/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate inside the machine room | 10/28/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs to be self-locking and non-defeatable | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide certified type ABC fire extinguisher inside the machine room | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Replace plunger seals. Plunger seals leak excessively and pit collection container has overflowed. | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell do not operate | 10/21/2021 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not illuminate | 10/28/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and bell do not operate. |