Inspection
Inspection Details
Equipment ID
19491
19491
Inspection Date
12/15/2020
12/15/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Douglas Miller
Douglas Miller
Relief Valve Pressure
600
600
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
7b78235f-e5fe-4bdd-8356-e5897a54932c
7b78235f-e5fe-4bdd-8356-e5897a54932c
Location
Evans Commons
209 S. Kingshighway Street, St. Charles, MO
Phone: (000) 000-0000
209 S. Kingshighway Street, St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: Lindenwood University
Lindenwood University
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Email: JNorman@lindenwood.edu
Lindenwood University
209 S KINGSHIGHWAY ST, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Email: JNorman@lindenwood.edu
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | An MCP shall be in place as specified in A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 | 1/7/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 1/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 1/31/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an overspeed valve. Based on the installation date of 2009, a category 5 test is due on the overspeed valve or before the next annual inspection. | 1/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 3.26.10 (Auxiliary Power)(Re-Inspection) | Yes | No | The auxiliary power lowering operation shall be functional. | 3/27/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/5/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 2.14.5 | Yes | No | The horizontal clearance shall not exceed .5" between the car side of the car door panel and the related car entrance jamb. Note: Both the right and left hand panels of this center opening car door fail to meet this requirement. The right hand car door, when in the normal open position, is open beyond the car entrance jamb, and because of this the clearance is several inches, and poses a potential pinch hazard. | 1/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room in a non-combustible frame with a clear protective vision plate over it. | 1/21/2026 |