Inspection
Inspection Details
Equipment ID
25089
25089
Inspection Date
11/25/2020
11/25/2020
Inspection Type
New Installation
New Installation
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Matthew Secrest
Matthew Secrest
Relief Valve Pressure
Slide
13"
13"
Governor Rope Pull
n/a
n/a
Door Closing Force
n/a
n/a
External ID
90f0d4d1-67e4-4528-b769-27ecd8d6e2e9
90f0d4d1-67e4-4528-b769-27ecd8d6e2e9
Location
American Electric
302 North 3rd Street, St Joseph, MO
Phone: (913) 642-6000
302 North 3rd Street, St Joseph, MO
Phone: (913) 642-6000
Owner
Attn: Wes Grammer
302 North 3rd Street, LLC
P.O Box 22876, Kansas City, MO 64113
Phone: (913) 642-6000
302 North 3rd Street, LLC
P.O Box 22876, Kansas City, MO 64113
Phone: (913) 642-6000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.10.2.2.2(hh) | Yes | No | only witnessed the weight test for this elevator, they were not ready for final inspection, need to test everything except for the weight test at the final reinspection | 2/22/2021 |
| A17.1-2016 : Elevators | 1.4 - Sills and car floor | 8.10.2.2.1(d) | No | No | car floor not installed | 12/7/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | standby power not tested | 12/7/2021 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | Yes | Yes | fire int. devices not tested | 12/7/2021 |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.10.2.2.1(o) | No | No | no in case of fire signage 2.27.9 | 12/7/2021 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | No | No | hoistway smoke damper not checked | 12/7/2021 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 8.10.2.2.2(hh) | Yes | No | gov pull thru test not done | 12/7/2021 |
| A17.1-2016 : Elevators | 2.29 - Car and counterweight safeties | 8.10.2.2.2(ii) | Yes | Yes | didnt test safties | 12/7/2021 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | No | No | not enough working room betweem disconnect an transformer | 12/7/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 2/22/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State certificate in machine room | 2/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell did not work on battery power, mechanic put in new battery and the alarm bell still didn’t work, troubleshoot and repair battery backup system | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Replace lightbulb in spotlight on top landing for the controller space illumination above car #2 entrance, it was not working | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Governor rope needs to shortened, tail sheave is about to trip the switch. |