Inspection
Inspection Details
Equipment ID
4221
4221
Inspection Date
12/29/2020
12/29/2020
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Donald Brown
Donald Brown
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
23
23
External ID
ad514a23-f6ee-42ec-ab3d-b29f3229f755
ad514a23-f6ee-42ec-ab3d-b29f3229f755
Location
Truman Farm Villa Apt
5318 HARRY S TRUMAN DR, GRANDVIEW, MO
Phone: (816) 966-0500
5318 HARRY S TRUMAN DR, GRANDVIEW, MO
Phone: (816) 966-0500
Owner
Attn: Peak Living Truman Farm Villas
Peak Living Truman Farm Villas
2174 W Grove Pkwy, Ste 100, Pleasant Grove, UT 84062
Phone: (385) 375-3255
Email: trumanfarmcm@peakliving.com
Peak Living Truman Farm Villas
2174 W Grove Pkwy, Ste 100, Pleasant Grove, UT 84062
Phone: (385) 375-3255
Email: trumanfarmcm@peakliving.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | replace missing hoistway door pick up rollers on all floors | 2/4/2019 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service test and post the log in the machine room | 2/20/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post a new copy of the state operating certificate in the elevator machine room every year | 2/11/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire caulk all penetrations in the machine room walls to maintain the fire rating of the room, new holes have been made that were not fire caulked | 2/11/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | monthly fire service test log is not posted in the machine room, perform fire service test monthly and keep a test log in the machine room | 1/27/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emergency phone had a dial tone but could not complete the call | 12/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | emergency light and bell battery is dead, replace the battery | 12/13/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | In case of fire don't use elevator signage needed | 3/7/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Below 10 foot candles | 3/7/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine room fire extinguisher out of date | 3/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)8 | No | No | Pit sump hole needs cover | 3/7/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit full of water. Remove and complete annual inspection. | 5/28/2026 |