Inspection
Inspection Details
Equipment ID
20117
20117
Inspection Date
7/21/2017
7/21/2017
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Relief Valve Pressure
595
595
Slide
Governor Rope Pull
Door Closing Force
24F 28R
24F 28R
External ID
Location
Cass Medical Center
2800 East Rock Haven, Harrisonville, MO
Phone: (816) 332-7121
2800 East Rock Haven, Harrisonville, MO
Phone: (816) 332-7121
Owner
Cass Medical Center
2800 East Rock Haven, Harrisonville, MO 64701
2800 East Rock Haven, Harrisonville, MO 64701
Billing
Attn: CASS MEDICAL CENTER
2800 EAST ROCK HAVEN, , MO 64701
2800 EAST ROCK HAVEN, , MO 64701
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | All elevators on EP Generator. Could not test Power Transfer due to surgery schedules. Must reschedule EP transfer test. | 7/28/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Standby power not tested | 3/7/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Rear car door restrictor is broken needing parts | 9/28/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | oil on pit floor | 4/26/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | unable to test emg. ppower at time of insp | 10/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | emg. power illumination lt. not working | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Telephone not functioning outside line not active. Must re-inspect. | 7/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency Power Operation & Transfer Switch could not be witnessed on the day selected for the annual inspection must reschedule. | 7/7/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Elevator pit floor shall be free of oil & debris. Inverted Piston oil containers shall not b e allowed to overflow. | 10/7/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone |