Inspection
Inspection Details
Equipment ID
8401
8401
Inspection Date
1/7/2021
1/7/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Stephen Long
Stephen Long
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
25
25
External ID
ebe0e8ca-134a-4da4-8b78-b08a1a955a4c
ebe0e8ca-134a-4da4-8b78-b08a1a955a4c
Location
US Bank- Joplin
402 MAIN ST, JOPLIN, MO
Phone: (816) 521-3387
402 MAIN ST, JOPLIN, MO
Phone: (816) 521-3387
Owner
Attn: US BANK
US BANK
3640 S NOLAND RD STE 200, INDEPENDENCE, MO 64055
Phone: (816) 521-3387
Email: sherri.mast@usbank.com
US BANK
3640 S NOLAND RD STE 200, INDEPENDENCE, MO 64055
Phone: (816) 521-3387
Email: sherri.mast@usbank.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | x | telephone not working--reinspect required | 7/23/2018 | |
| conversion | conversion | n/a | bearings in motor need to be changed | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | 1.6-telephone does not work | 7/26/2019 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | x | telephone will not call out | 1/7/2021 | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | needs current certificate posted in machine room | |||
| MO Minimum : Elevators | (I) - Pits | (I)1 | 1/7/21 : Excessive debris in pit | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | 1/7/21 replace damaged door operator belt | |||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | 1/7/21 2-way communication device shall work and give proper location | 8/25/2023 | |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | x | 1/7/21 Detector edge shall be bypassed on fire service. | 8/25/2023 | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | 1/7/21 Unused escutcheon holes in hoistway doors shall be filled | |||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Must Post Current State operating Cert. 5.100(2) | |||
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Must make car door restrictor Operable. 8.6.4.13.1(I) | 8/22/2024 | |
| A17.1-2016 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 8.6.4.13.1(l)(Door Restrictor) | x | Must make Car door restrictor operable. |