Inspection
Inspection Details
Equipment ID
6784
6784
Inspection Date
5/21/2018
5/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Dustin Schmidt
Dustin Schmidt
Relief Valve Pressure
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
27
27
External ID
dbdcc26b-16f2-42f2-83bf-885fecfe60f2
dbdcc26b-16f2-42f2-83bf-885fecfe60f2
Location
Shell Building
1221 LOCUST ST, SAINT LOUIS, MO
1221 LOCUST ST, SAINT LOUIS, MO
Owner
Shell Building Partnership
1221 LOCUST ST, SAINT LOUIS, MO 63103-2343
1221 LOCUST ST, SAINT LOUIS, MO 63103-2343
Billing
Attn: Shell Building
1221 LOCUST ST, SAINT LOUIS, MO 63103-2343
1221 LOCUST ST, SAINT LOUIS, MO 63103-2343
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Existing cab emergency telephone does not work and shall be repaired and tested. | 5/30/2019 | |
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | In car emergency phone shall work. | 5/8/2020 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display a current state operating certificate. | 11/17/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | The pit lighting shall be operational. | 11/17/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | The machine room door shall be self-locking. | 11/17/2022 | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 12/15/2021 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | The machine room lighting shall not be less than 10 ftc at the floor of the machine room. | 11/17/2022 | ||
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Provide annual testing of elevators on emergency power. | 2/23/2023 | |
A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Provide MCP. | 8/14/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | Independent riser push button on door buck has broken halo ring,repair as needed | 8/14/2023 | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Elevator appears to have emergency generator power, which needs to be scheduled and tested. Re-inspection required | 2/2/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | Emergency exit cover switch shall be operable. Repair/replace same. Re-inspection required | |||
MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | Emergency phone in elevator was not answered, phone not working. Re-inspection required | 2/2/2024 | |
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Need to provide testing of fire service to complete inspection. Re-inspection required | 2/2/2024 | |
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.13 - Emergency exit | 2.14.1.5 | x | Car top emergency exit not code compliant, make so. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | Clean the car top. | |||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | x | Door restrictor out of adjustment, repair or replace as needed. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone works, but is requesting keypad entry, reprogram. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Provide Cat 1 testing of the elevator on emergency power. | ||
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | x | Provide Cat 1 testing of the emergency power selector switch. |