Inspection
Inspection Details
Equipment ID
16827
16827
Inspection Date
6/15/2018
6/15/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
John Ryan
John Ryan
Mechanic Name
Kenneth Gustavson
Kenneth Gustavson
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
bf1c6706-64b6-49ae-b305-9feda2702657
bf1c6706-64b6-49ae-b305-9feda2702657
Location
Interiors Unlimited
2149 SCHUETZ RD, SAINT LOUIS, MO
2149 SCHUETZ RD, SAINT LOUIS, MO
Owner
Sherwin Williams
2145 SCHUETZ RD, SAINT LOUIS, MO 63146-3515
2145 SCHUETZ RD, SAINT LOUIS, MO 63146-3515
Billing
Attn: Sherwin Willliams
2145 SCHUETZ RD, SAINT LOUIS, MO 63146-3515
2145 SCHUETZ RD, SAINT LOUIS, MO 63146-3515
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | In car emergency bell shall work. | 6/28/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency bell and light shall be operational. | 2/12/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. | 5/21/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 2/28/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Top floor door pickup roller shall be replaced. | 5/22/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water on pit floor shall be removed. The pit shall be kept clean and dry. | 5/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired. An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 5/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | A code data plate shall be provided on the machine. | 5/22/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | All pits shall be kept dry, clean and free of equipment or materials not relating to the operation of the elevator. | 5/9/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit has approximately 12" of water. Pit shall be kept dry, remvove rust from pit equipment, repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak. | |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Pit sump pump is not working. Repair/replace as needed. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light shall work. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | All cab lighting lamps shall work. 1 of 2 lamps not working. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Machine room walls covered in mold up to about 3' above the floor. Clean/replace as needed. |