Inspection
Inspection Details
Equipment ID
22680
22680
Inspection Date
1/14/2021
1/14/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
7
7
Governor Rope Pull
28/360
28/360
Door Closing Force
20
20
External ID
d61f0855-fc99-46e4-b9d0-b6da2ce220c6
d61f0855-fc99-46e4-b9d0-b6da2ce220c6
Location
Whole Foods
4577 West Pine Blvd, SAINT LOUIS, MO
Phone: (314) 474-7300
Email: shawn.milford@wholefoods.com
4577 West Pine Blvd, SAINT LOUIS, MO
Phone: (314) 474-7300
Email: shawn.milford@wholefoods.com
Owner
Attn: The Dedicated Orion, LP
The Dedicated Orion, LP
4567 W Pine Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
The Dedicated Orion, LP
4567 W Pine Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair Basement Floor Hall sill trip Hazard | 7/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | Yes | No | Counterweights bottom out before car reaches its final limit. Repair | 12/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written maintenance control program shall be kept on site for each elevator. | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | No | No | Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees. | 9/15/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency generator testing shall be performed. Re-inspection required | 2/3/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Access to the elevator disconnects shall be unobstructed | 9/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The door to the elevator disconnects shall be self closing & self locking | 9/15/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | No flammable materials are to be stored in the elevator disconnect room | 9/15/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 8.11.2.1.3(s) | No | No | Sill guards are missing at the bottom of all hoistway door landing sills. Guards shall be the length of the car leveling zone, plus 3 inches, and be beveled at an angle between 60 and 75 degrees. Previous violations from past years. | 9/15/2025 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency generator testing shall be performed. Re-inspection required.Previous violations from past years. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 2.11.11.1 | No | No | Repair Bottom Floor Trip hazard at hall sill. Previous violation from past years. | 9/15/2025 |