Inspection
Inspection Details
Equipment ID
14892
14892
Inspection Date
1/7/2021
1/7/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Robert Kehm
Robert Kehm
Mechanic Name
John Hambrough
John Hambrough
Relief Valve Pressure
Slide
12"
12"
Governor Rope Pull
60/400
60/400
Door Closing Force
18
18
External ID
046eb9b0-1122-48e5-b46d-45b4dc628206
046eb9b0-1122-48e5-b46d-45b4dc628206
Location
City View Apts #20
1600 Pine St, Bldg 20, St. Louis, MO
Phone: (314) 588-1177
1600 Pine St, Bldg 20, St. Louis, MO
Phone: (314) 588-1177
Owner
Attn: Mills Properties Inc Cityview Apartments
Mills Properties Inc Cityview Apartments
110 N 17TH ST, SAINT LOUIS, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Mills Properties Inc Cityview Apartments
110 N 17TH ST, SAINT LOUIS, MO 63103
Phone: (314) 588-1177
Email: cityviewmanager@millsproperties.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.11.2.1.3(cc)(3) Replace when diameter is reduced (Re-Inspection) | Yes | No | The suspension ropes have excessive rouging and have reached the minimum acceptable diameter. The suspension ropes shall be replaced. | 10/12/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | 2/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Evacuation procedures are missing from the MCP. | 2/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/11/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Rooms and Machinery Spaces | No | No | The machine room shall be kept clean. Clean the machine room and remove all non-elevator related items. | 2/11/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. | 3/11/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational (2nd Notice). Per Chief Inspector Gus Guadamuz, 14 days to fix phones or individual units will start being taken out of service. | 8/27/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door lock is broken and must be repaired to prevent access to machine room by unauthorized persons. Access doors shall be self-closing and self-locking. | 4/27/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | A permanent and unobstructed means of access shall be provided in machine room (debris and non-elevator related material impeding access to ladder to machine room). | 4/27/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door lock is broken and must be repaired to prevent access to machine room by unauthorized persons. Access doors shall be self-closing and self-locking. |