Inspection
Inspection Details
Equipment ID
23588
23588
Inspection Date
1/4/2021
1/4/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
28
28
External ID
c23f6d96-2cce-46f0-b626-d93347bc13e4
c23f6d96-2cce-46f0-b626-d93347bc13e4
Location
Worp/CA Clayton Property Owner LLC
212 S MERAMEC AVE, CLAYTON, MO
Phone: (314) 721-1212
212 S MERAMEC AVE, CLAYTON, MO
Phone: (314) 721-1212
Owner
Worp/Ca Clatyton Property
20 W JACKSON BLVD, CHICAGO, IL 60604-3908
20 W JACKSON BLVD, CHICAGO, IL 60604-3908
Billing
Attn: Worp/Ca Clatyton Property
212 S MERAMEC AVE, CLAYTON, MO 63105-3513
212 S MERAMEC AVE, CLAYTON, MO 63105-3513
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Provide code compliant minimum counterweight runby. | 10/29/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide pit ladder rungs to be non-slip type. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2 Design and Construction of Pits | No | No | Provide code compliant pit lighting. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Standby power operation of the elevator shall be tested. | 8/10/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | No | No | Hoistway walls shall have smooth surfaces. Drywall screws shall not protrude into the hoistway. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Car Tops | No | No | The top of the car and the hoistway shall be cleaned. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | The pit shall be kept clean. Clean the pit. | 2/6/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 1/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.5 - Housekeeping | 8.6.4.7 Cleaning of Hoistways and Pits | No | No | Top of the car, hoistway, and doors shall be cleaned (excessive rope rouge). | 4/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kept clean. Remove excess debris. | 4/19/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed in the machine room in a non-combustinble frame. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.4 - Machine space | 2.1.3.3 | No | No | Wiring for the cellular gateway is draped across control space and needs to be re-routed around the perimiter of space and properly supported. |