Inspection
Inspection Details
Equipment ID
12310
12310
Inspection Date
1/25/2021
1/25/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Steve Wiseman
Steve Wiseman
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
21
21
External ID
b859ed42-2f36-4a13-bd6e-85d6ae4b2889
b859ed42-2f36-4a13-bd6e-85d6ae4b2889
Location
Royal Vista
31 ROYAL VISTA DR, BRANSON, MO
Phone: (417) 886-8606
31 ROYAL VISTA DR, BRANSON, MO
Phone: (417) 886-8606
Owner
Attn: Royal Vista Condo Association
Royal Vista Condo Association
PO Box 2182, Branson West, MO 65737
Phone: (417) 294-1913
Alt Phone: (417) 332-7857
Email: royalvistacoa@gmail.com
Royal Vista Condo Association
PO Box 2182, Branson West, MO 65737
Phone: (417) 294-1913
Alt Phone: (417) 332-7857
Email: royalvistacoa@gmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair the non working GFCI on the car top. | 5/1/2019 |
| conversion | conversion | n/a | No | No | Obtain and display a current state operating certificate in the machine room | 5/1/2019 |
| conversion | conversion | n/a | No | No | Repair the emergency phone yours does not work | 5/1/2019 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 1001.2(b)(1) | No | No | Remove the added dead bolt from the macnine room door. | 5/1/2019 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Replace the burnt out pit light. | 8/13/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | REplace the burnt out light bulb in the pit | 11/1/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | REmove the existing dead bolt from the machine room door and install a lever latch with a machnical room door lock always locked outside never locked inside. along with a closer as it is to be self closing self latching. | 11/1/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 11/1/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replace the emergency phone as there is no dial tone. | 1/25/2021 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(d) | No | No | Provide a maintenance control program in the machine room | 11/1/2020 |
| A17.1-1996 : Elevators | 1.14 - Ventilation | 1001.2(a)(14) | No | No | Replace the bad exhaust fan in the car top. This ones froze up. | 11/1/2020 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Remove the mold in the machine room ceiling and replace the drywall thats falling down to provide a min of 1 hour rated assembly | 2/16/2022 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | Repair the hole cut into the wall to the right of the machine room door back to a 1 hour rating. | 2/16/2022 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a | No | No | cover the exposed wood around the new machine room door to provide a min of 1 hour assembly | 2/16/2022 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3d | No | No | Remove the dead bolt from the machine room door as it is to be a self closing self locking spring type lock always locked outside never locked inside. | 9/8/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as there is no dial tone. | 7/8/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Repair or replace the emergency phone as there is no line voltage. its dead. | 8/15/2022 |