Inspection
Inspection Details
Equipment ID
7152
7152
Inspection Date
1/20/2021
1/20/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
Slide
5 1/2
5 1/2
Governor Rope Pull
150/990
150/990
Door Closing Force
25
25
External ID
a876f782-c625-4900-9ed6-ae8068038d99
a876f782-c625-4900-9ed6-ae8068038d99
Location
HoteLumiere
901 N 1st St, St. Louis, MO
Phone: (314) 881-7777
901 N 1st St, St. Louis, MO
Phone: (314) 881-7777
Owner
Attn: UNK
Pinnacle Entertainment
3800 HOWARD HUGHES PKWY, LAS VEGAS, NV 89169
Phone: (000) 000-0000
Pinnacle Entertainment
3800 HOWARD HUGHES PKWY, LAS VEGAS, NV 89169
Phone: (000) 000-0000
Billing
Attn: HoteLumiere
HoteLumiere
901 N 1ST ST, SAINT LOUIS, MO 63102
Phone: (314) 881-7870
Email: Maiazzi@lumiereplace.com
HoteLumiere
901 N 1ST ST, SAINT LOUIS, MO 63102
Phone: (314) 881-7870
Email: Maiazzi@lumiereplace.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean oil off of floor and machine. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace broken clutch roller and 4th floor. | 11/26/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated cert in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Clean cartop of dirt and debris. | 11/26/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lights shall be guarded. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wire in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door should be self closing and locking. | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wires in machine room. | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light and alarm bell do not work. | 4/19/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace clutch rollers on doors for floor 4 and 7 | 11/26/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lights not adequate | 11/26/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency back up lights not working. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. Re-inspection required | 12/20/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, needs to be serviced or replaced. | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. Re-inspection required | 1/12/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Clean machine room floor of oil leaking from machine, need to repair leaks | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean cartop | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car need to be guarded to protect passengers in event of bulb breakage, install solid ceiling panels of plastic tubes and endcaps | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wires in machine room shall be enclosed in conduit or electrical boxes | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self locking and self closing | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit lights are not working | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove water from pit. Repair / replace sump pump | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car side selector cable is rusted from water in pit, needs replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car buffer channel is rusting out due to water in pit. Refurbish/replace same | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made to work when car looses 110 vac. Re-inspection required | 1/8/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall be made to work car looses 110vac. | 4/28/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate has been expired for several years. A copy of current valid certificate needs to be displayed in machine room. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Clean machine room floor of oil leaking from machine, repair leaks. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Clean car top | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car need to be guarded to protect passengers in event of bulb breakage, install solid ceiling panels of plastic tubes and endcaps. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)7 | No | No | Exposed wires in machine room shall be enclosed in conduit or electrical boxes. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and locking. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light in pit shall work | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove water from pit. Repair/replace sump pump | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car side selector cable is rusted from water in pit. Replace same. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car buffer channel is rusting out due to water in pit. Refurbish/replace same. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | Yes | The elevator was removed from service for having existing violations for consecutive years in a row. All violations shall be corrected before the elevator is returned to service and the annual insepection is completed. | 4/28/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Bell and Phone not Functioning (Red Tag) | Yes | Yes | Elevator cab phone does not work on normal or back-up power. Elevator has not had a phone for over a year and a half. Elevator Red-tagged and removed from service. Re-inspection required | 7/3/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.9 Cleaning of Top of Cars | No | No | Need to clean cartop | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Light bulbs in car need to be guarded to protest passengers in event of bulb breakage, install solid ceiling panels of plastic tubes and endcaps | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Exposed wires in machine room shall be enclosed in conduit or electrical boxes | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and locking | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car side selector cable is rusted from water in pit. Need to be replaced | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean cartop of dirt and debris. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wire in machine room. Need to be enclosed in conduit or electrical boxes | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Car side selector cable is rusted from water in the pit, needs to be replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Machine need cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Car side selector cable is rusted and shall be replaced | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Car light shall be guarded | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Exposed wired for AC/Thermostat shall be enclosed in conduit and boxes | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top needs cleaned |