Inspection
Inspection Details
Equipment ID
405
405
Inspection Date
6/26/2018
6/26/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wendy Eiss
Wendy Eiss
Mechanic Name
Richard Rickermann
Richard Rickermann
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
ee65893e-7df8-4819-a2da-3b10aa8c10a1
ee65893e-7df8-4819-a2da-3b10aa8c10a1
Location
Verkamp & Malone LLC
401 W 5TH ST, ROLLA, MO
401 W 5TH ST, ROLLA, MO
Owner
Verkamp & Malone LLC
401 W 5TH ST, ROLLA, MO 65401-3007
401 W 5TH ST, ROLLA, MO 65401-3007
Billing
Attn: Verkamp & Malone LLC
PO BOX 32, ROLLA, MO 65402-0032
PO BOX 32, ROLLA, MO 65402-0032
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Need "In Case of Fire" signs by each Hall call button | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Mold on the machine room walls must be addressed. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | "In Case of Fire" signage is required at all landings. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Looks like the pit has flooded in the past. The hydraulic oil in the tank shall be checked from water contamination. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall be operational. | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light appears to have been underwater and does not work, needs repair. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Need to install cover on light switch to prevent against electrical shock in machine room per national elevator code | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The drywall shall be replaced in the machine room. The bottom half of the drywall has been removed throughout the machine room and has never been replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, have serviced or replaced | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light appears to have been underwater and does not work, need to repair the elevator pit light. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | A sump pump is needed to remove water from the pit. | |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Pit channels and buffers need to be replaced due to years of water damage | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light appears to have been underwater and does not work, needs repair. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The drywall shall be replaced in the machine room. The bottom half of the drywall has been removed throughout the machine room and has never been replaced | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher is expired, have serviced or replaced |