Inspection
Inspection Details
Equipment ID
871
871
Inspection Date
1/28/2021
1/28/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Timothy Trout
Timothy Trout
Mechanic Name
Steve Wiseman
Steve Wiseman
Relief Valve Pressure
360
360
Slide
Governor Rope Pull
Door Closing Force
27
27
External ID
6b28dd61-a6b4-4308-a982-bcfcb871662f
6b28dd61-a6b4-4308-a982-bcfcb871662f
Location
Emerald Bay Yacht Club
654 EMERALD POINTE DR, HOLLISTER, MO
Phone: (501) 626-7454
654 EMERALD POINTE DR, HOLLISTER, MO
Phone: (501) 626-7454
Owner
Emerald Bay Yacht Club
9554 N HUNTER AVE, KANSAS CITY, MO 64157-7958
9554 N HUNTER AVE, KANSAS CITY, MO 64157-7958
Billing
Attn: Emerald Bay Yacht Club
9554 N HUNTER AVE, KANSAS CITY, MO 64157-7958
9554 N HUNTER AVE, KANSAS CITY, MO 64157-7958
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace the burnt out light tubes in the car ceiling. | 2/4/2020 |
| conversion | conversion | n/a | No | No | Repair the GFCI recptical in the pit as it does not work | 2/4/2020 |
| conversion | conversion | n/a | No | No | Replace the burnt out li9ght bulb in the pit light. | 2/4/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room | 12/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 12/1/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a curren state operating certificate in the machine room. | 1/3/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Have the fire extinguisher re-certified it is expired. | 1/3/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | REplace the missing smoke detector in the machine room, have reconnected to the elevator and have re-inspected in 14 days. | 4/4/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Have the emergency phone repaired and call for re-inspection within 14 days. the incoming line is dead. | 4/4/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Obtain and display a current state operating certificate in the machine room. | 1/3/2024 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Have the fire extinguisher re-certified yours expired in 21. | 1/3/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone as there is no dial tone. this requires a re-inspection within 14 days. | 6/14/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | Yes | No | Replace the missing smoke detector in the machine room | 6/14/2023 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | No | No | Have the fire extinguisher re-certified it has expired | 4/4/2024 |