Inspection
Inspection Details
Equipment ID
16907
16907
Inspection Date
5/21/2018
5/21/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Edward Barfield
Edward Barfield
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
a5184e70-05b3-4836-ab42-d07b107cd578
a5184e70-05b3-4836-ab42-d07b107cd578
Location
Senior Livings & Gardens @ Renaissance
3217 MARTIN LUTHER KING DR, ST. LOUIS, MO
3217 MARTIN LUTHER KING DR, ST. LOUIS, MO
Owner
McCormack, Baron, Ragan
720 OLIVE ST, SAINT LOUIS, MO 63101-2338
720 OLIVE ST, SAINT LOUIS, MO 63101-2338
Billing
Attn: Blumeyer Elderly
3217 MARTIN LUTHER KING, ST. LOUIS, MO 63106
3217 MARTIN LUTHER KING, ST. LOUIS, MO 63106
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
conversion | conversion | conversion - reinspect | x | In car emergency telephone shall work. | 5/21/2018 | |
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | Remove the oil & water from the pit. The pit shall be kept clean and dry. | 3/1/2021 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed on this unit on or before the next annual inspection. | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | The auxiliary battery lowering shall be operational. | 11/16/2022 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | Where additional power sources is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. (Confirm operation and correct if needed). | |||
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 9/27/2023 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | x | Where additional power sources is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. | 9/27/2023 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State operating certificate in machine room. | |||
A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1206.1h | Provide current tested fire extinguisher in machine room. | |||
A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1002.2f | x | Machine room smoke detectors shall be operational. Smoke detector is currently covered and preventing it from being operational. | 9/27/2023 | |
A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | x | Where auxiliary lowering operating is provided, it shall conform to 3.26.10.1 through 3.26.10.3. | 6/12/2024 | |
A17.1-1996 : Elevators | 2.11 - Disconnecting Means and Control | 210.4 | x | Where additional power sources is connected to load side of disconnect, it shall have an auxiliary contact to prevent battery lowering from energizing when disconnect is opened. | 6/12/2024 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Up-to-date operating certificate required in the machine room. | |||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | The pit shall be kept clean. | |||
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. |