conversion
|
conversion
|
n/a
|
|
|
Place state certificate in machine room.
|
3/4/2019
|
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Phone in elevator cab does not work. Repair.
|
8/6/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV not tagged or sealed. Perform OSV test on or before next annual inspection.
|
1/24/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work as intended. Phone dials out then goes to a busy/disconnected signal. Repair or replace
|
12/21/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevators that are equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power, annually.
|
7/15/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
2/24/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevator failed to operate on the emergency generator. Take corrective action and re-test.
|
12/13/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
2/24/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevator failed to operate on the emergency generator. Take corrective action and re-test. (2nd Notice)
|
2/24/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pits shall be kept clean, dry, and free of debris and oil.
|
2/24/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevator failed to operate on the emergency generator. Take corrective action and re-test
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing
|
2.14.1.7 Railing and Equipment on Top of Cars
|
|
|
handrail system shall be installed on car top. Distance is greater than 12 inches from car top to hoistway wall.
|
|