Inspection
Inspection Details
Equipment ID
1747
1747
Inspection Date
1/25/2021
1/25/2021
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Charles Sheriff
Charles Sheriff
Relief Valve Pressure
Slide
7"
7"
Governor Rope Pull
120/560
120/560
Door Closing Force
20/18
20/18
External ID
698f2c51-66d7-4f10-9eb8-ac673b34145d
698f2c51-66d7-4f10-9eb8-ac673b34145d
Location
St. Louis Altenheim
5408 S BROADWAY, SAINT LOUIS, MO
Phone: (314) 353-7225
5408 S BROADWAY, SAINT LOUIS, MO
Phone: (314) 353-7225
Owner
St. Louis Altenheim
5408 S BROADWAY, SAINT LOUIS, MO 63111-2023
5408 S BROADWAY, SAINT LOUIS, MO 63111-2023
Billing
Attn: St. Louis Altenheim
5408 S BROADWAY, SAINT LOUIS, MO 63111-2023
5408 S BROADWAY, SAINT LOUIS, MO 63111-2023
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.1 | Yes | No | Counterweight runby is 1". Minimum required is 6" | 4/16/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | PHONE SHALL ALLOW FOR 2-WAY COMMUNICATION. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.6.2.5 | Yes | No | Shorten Hoist Ropes. Where spring buffers are used, bottom runby shall be not less than 6". | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self-closing and self-locking . Door does not latch. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Machine room lighting needs to be repaired, 1 or more bulbs not working. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag. (Expired) | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Fire Service Testing must be documented monthly. The form is present in the MCP, but hasn't been logged monthly. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 8.6.4.13 Door Systems | Yes | No | Hoistway door has loose guide on 2R floor. Repair/replace as needed. | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 2.20 | No | No | Hoist Ropes are dry and showing “rouge” and "dusting" on floor. Ropes shall be cleaned and lubricated per OEM recommendations | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.7 - Car door or gate | 2.14.4 | No | No | Adjust upthrust roller bearings for proper clearance to door hanger track.(all floors). | 8/7/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.23 - Suspension rope | 8.6.2.5 | Yes | No | Shorten Hoist Ropes. Where spring buffers are used, bottom runby shall be not less than 6". | 8/31/2026 |