Inspection
Inspection Details
Equipment ID
14349
14349
Inspection Date
1/13/2021
1/13/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Edward Balsat
Edward Balsat
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
4d6a3ae1-e4f0-4f64-881b-aa20ee952953
4d6a3ae1-e4f0-4f64-881b-aa20ee952953
Location
Magellan Behavioral Health
14100 Magellan Plz, Maryland Heights, MO
Phone: (314) 574-4252
14100 Magellan Plz, Maryland Heights, MO
Phone: (314) 574-4252
Owner
Magellan Behavioral Health
14100 MAGELLAN PLZ, MARYLAND HEIGHTS, MO 63043-4644
14100 MAGELLAN PLZ, MARYLAND HEIGHTS, MO 63043-4644
Billing
Attn: Magellan Behavioral Health
14100 MAGELLAN PLZ, MARYLAND HEIGHTS, MO 63043-4644
14100 MAGELLAN PLZ, MARYLAND HEIGHTS, MO 63043-4644
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Provide a code compliant MCP including onsite documents. | 2/15/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. | 2/15/2021 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | The in car emergency lighting shall be operational. | 4/16/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency alarm bell shall be operational with the 110v source removed. | 4/16/2021 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 9/18/2025 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 9/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room. | 9/18/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car is not working. | 9/18/2025 |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 3/9/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1206.7 | No | No | A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. | 3/9/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.7 Record of Oil Usage | No | No | A written record shall be kept of the quantity of hydraulic fluid added to the system and emptied from leakage collection containers and pans. The written record shall be kept in the machine room. | 3/9/2026 |