Inspection
Inspection Details
Equipment ID
9431
9431
Inspection Date
7/11/2018
7/11/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
John Osowski
John Osowski
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
f-22 r-25
f-22 r-25
External ID
e2ee185c-78e3-4de4-9f0b-50b151f8c903
e2ee185c-78e3-4de4-9f0b-50b151f8c903
Location
Bates County Courthouse
1 N DELAWARE ST, BUTLER, MO
1 N DELAWARE ST, BUTLER, MO
Owner
Bates County of
1 N DELAWARE ST, BUTLER, MO 64730-2266
1 N DELAWARE ST, BUTLER, MO 64730-2266
Billing
Attn: Bates County of
1 N DELAWARE ST, BUTLER, MO 64730-2266
1 N DELAWARE ST, BUTLER, MO 64730-2266
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | No | No | emergency light and bell failed | 1/16/2020 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.4 Instructions for Locating Maintenance Records | No | No | no testing procedures no valve info | 7/31/2021 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No current city. Posted | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Battery lowering not working | 1/19/2024 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2(c)(5) | No | No | Need test procedure for overspeed valve | |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.4.19.6 | Yes | No | both car doors open or closed from either set of car buttons at same time at floor with opposed openings | 1/19/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | Emg Battery lowering not working | 7/8/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | when at a floor with both front an rear doors at that foor both front an rear doors open at the same time. | 7/8/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | pit lt not working | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | Yes | No | couldnt test emg power at time of insp | 6/13/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | fire ext. out of date needs checked annually |