Inspection
Inspection Details
Equipment ID
23053
23053
Inspection Date
2/4/2021
2/4/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Bill Suedkamp
Bill Suedkamp
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
18
18
External ID
46e30779-df9f-445c-9f45-0a32c286627c
46e30779-df9f-445c-9f45-0a32c286627c
Location
Lindell Residences LLC
4653 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 930-2001
4653 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 930-2001
Owner
Attn: Lindell Residences LLC
Lindell Residences LLC
4643 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (314) 833-8999
Email: lbright@apcliving.com
Lindell Residences LLC
4643 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (314) 833-8999
Email: lbright@apcliving.com
Billing
Attn: Lindell Residences LLC
Lindell Residences LLC
4643 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (314) 833-8999
Email: allison.mangiore@assetliving.com
Lindell Residences LLC
4643 LINDELL BLVD, SAINT LOUIS, MO 63108
Phone: (314) 833-8999
Email: allison.mangiore@assetliving.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | install test tag on governor showing date of acceptance test. | 1/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.13 - Governor,overspeed switch and seal | 2.18 | Yes | No | governor remote trip does in controller does not work. repair. | 1/9/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Clean elevator pit. | 5/24/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Emergency evacuation battery pack needs replaced. Re-inspection required | 3/6/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be on display in the machine room | 3/20/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not operable, needs repaired. Re-inspection required | 4/4/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 3/2/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Need to test elevator operation while on emergency generator power operation. Re-inspection required | 4/4/2025 |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Need to install code data plate with required information | 3/2/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency Power shall be tested. | 3/2/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator on emergency power. | |
| A17.1-2016 : Elevators | 4.12 - Standby power selection switch | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide testing of the elevator emergency power selector switch (fire control room). | |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.18.4 | Yes | No | Means (solenoid) to remotely activate governor not working properly. |