Inspection
Inspection Details
Equipment ID
10131
10131
Inspection Date
2/9/2021
2/9/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Relief Valve Pressure
Na
Na
Slide
Governor Rope Pull
Door Closing Force
Na
Na
External ID
fac51ae2-ff63-4b57-b86a-6765ef0d0e85
fac51ae2-ff63-4b57-b86a-6765ef0d0e85
Location
Life Storage
6557 Manchester Ave, St. Louis, MO
Phone: (314) 646-1107
Email: elevators@lifestorage.com
6557 Manchester Ave, St. Louis, MO
Phone: (314) 646-1107
Email: elevators@lifestorage.com
Owner
Attn: Life Storage
Life Storage
6467 Main St, Buffalo, NY 14221
Phone: (716) 650-6139
Fax: (716) 810-8130
Email: elevators@lifestorage.com
Life Storage
6467 Main St, Buffalo, NY 14221
Phone: (716) 650-6139
Fax: (716) 810-8130
Email: elevators@lifestorage.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/9/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed and must have a cat 5 weight test performed | 12/1/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide existing machine room lights to work. | 2/19/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Remove all non elevator related items from the elevator machine room. | 2/19/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide existing battery backup lowering unit to work properly. | 10/7/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 2/19/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 3.26.10 | Yes | No | Repair inoperative ERU device | 2/19/2026 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Supply up to date serviced fire extinguisher | 2/19/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 3.27.1 Phase I Emergency Recall Operation After Device Actuation | Yes | Yes | Car emergency stop switch not overridden | 2/19/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Provide existing battery backup lowering unit (ERU) to work properly. | |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Provide current year tested fire extinguisher in the elevator machine room. | |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Car Emergency System (Re-Inspection) | Yes | No | Provide existing emergency lights and bell to work. |