Inspection
Inspection Details
Equipment ID
18573
18573
Inspection Date
2/17/2021
2/17/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Ken Koppel
Ken Koppel
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
NA
NA
External ID
502a26a7-8dc4-42ad-b621-c0b99d8caac1
502a26a7-8dc4-42ad-b621-c0b99d8caac1
Location
4545 Lindell
4545 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 361-8260
4545 LINDELL BLVD, SAINT LOUIS, MO
Phone: (314) 361-8260
Owner
Attn: Rodemeyer Christel Inc
4545 Lindell A Condominium
3630 Grandel SQ, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 318
Email: ABelsky@rcirealty.com
4545 Lindell A Condominium
3630 Grandel SQ, St. Louis, MO 63108
Phone: (314) 454-0800 Ext: 318
Email: ABelsky@rcirealty.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | Maintenance control program needs to include testing procedures | 12/6/2020 | ||
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Water line for outside faucet is not allowed in machine room | 12/6/2020 | ||
A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.2 | Where water line goes through wall in machine room, the fire rated assembly has been compromised | 12/6/2020 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Need testing procedures included in MCP on or before January 1, 2022 | 12/4/2023 | ||
A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(j) | Service Fire Extinguisher in machine room 8.6.1.6.5 | 12/21/2023 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 12/21/2023 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service test & document on log in machine room | 12/21/2023 | ||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | Provide a complete maintenance control plan to include testing procedures | 12/21/2023 | ||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in machine room | 12/21/2023 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | 12/21/2023 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current state certificate in machine room | |||
MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service testing and document on log in the machine room | |||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | Testb emergency generator | ||
A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Service fire extinguisher in the machine room |