Inspection
Inspection Details
Equipment ID
10428
10428
Inspection Date
7/11/2018
7/11/2018
Inspection Type
Alteration
Alteration
Inspector Name
Steven Voss
Steven Voss
Mechanic Name
Gerard Hussey
Gerard Hussey
Relief Valve Pressure
480
480
Slide
Governor Rope Pull
Door Closing Force
14
14
External ID
7db95be2-4be9-458a-bd77-1cf1ec082f2f
7db95be2-4be9-458a-bd77-1cf1ec082f2f
Location
St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO
10010 KENNERLY RD, SAINT LOUIS, MO
Owner
St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
Billing
Attn: St. Anthony's Medical Center
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
10010 KENNERLY RD, SAINT LOUIS, MO 63128-2106
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | There is no fireman?s emergency service phase I instruction signage adjacent to the keyed switch at the primary egress floor, as required. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. Per Asst. State Fire Marshall Greg Carrell, G.1 is the correct code section for this violation. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be repaired to properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 8/12/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The elevator pit shall be cleaned of dust and debris. | 10/20/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations were tested and the following deficiencies were noted: There is no fireman’s emergency service phase II instruction signage adjacent to the keyed switch in the car, as required | 8/12/2020 |
| MO Minimum : Elevators | (S) - Fire Service | (S)1 | Yes | No | The fireman's emergency service phase I and II operations were tested and the following deficiencies were noted: The “Door Open” button did not work in phase II. | 8/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The front car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 10/29/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. | 8/16/2022 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 8/4/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Generator testing and fire service shall be tested. Scheduled on 8/19/25 | 8/19/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 7/13/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. | 7/13/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | When sprinkler systems are present in the hoistway, means shall be provided to automatically disconnect the main power supply to the affected elevator prior to the application of water. A smoke detector shall also be installed to recall the elevator before the power is removed before the application of water. This is the 3rd consecutive year that this violation has been issued. Corrections SHALL be made in 30 days or the elevator will be removed from service due to not having a current certificate of compliance. Reinspection is required for compliance, |