Inspection
Inspection Details
Equipment ID
20116
20116
Inspection Date
7/10/2018
7/10/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
F. Scott Gibson
F. Scott Gibson
Mechanic Name
Christopher Bolin
Christopher Bolin
Relief Valve Pressure
500
500
Slide
Governor Rope Pull
Door Closing Force
F26 R27
F26 R27
External ID
d483bfe4-c2c9-4b45-b870-f6a2d996cceb
d483bfe4-c2c9-4b45-b870-f6a2d996cceb
Location
Cass Medical Center
2800 E ROCK HAVEN RD, HARRISONVILLE, MO
2800 E ROCK HAVEN RD, HARRISONVILLE, MO
Owner
Cass Medical Center
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701-4411
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701-4411
Billing
Attn: CASS MEDICAL CENTER
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701-4411
2800 E ROCK HAVEN RD, HARRISONVILLE, MO 64701-4411
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | All elevators on EP Generator. Could not test power transfer because of surgeries scheduled. Must reschedule EP transfer Test. | 7/28/2021 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | Standby power not tested | 3/7/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell not working | 10/2/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | couldnt test emg. power at time of insp | 10/2/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | emg power illumination lt. not working | 4/26/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Telephone not functioning outside line not active. Must Reinspect. | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Emergency Power Operation & Transfer could not be witnessed on the day of the annual inspection. Must set date for testing. Witnessed the Generator Test Log unit was last tested on 7/3/24 | 12/9/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2.3 (Elevator Emergency Power Illuminated Signal) | No | No | Illumanation lt didnt work | 9/12/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door must be self-locking | 9/12/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency alarm not working. Bad bell. Replace | 9/12/2025 |