Inspection
Inspection Details
Equipment ID
19103
19103
Inspection Date
2/24/2021
2/24/2021
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Thomas Moore
Thomas Moore
Relief Valve Pressure
NA
NA
Slide
Governor Rope Pull
Door Closing Force
NA
NA
External ID
1da2e2b5-c394-41a7-a91c-a63a1176a8b1
1da2e2b5-c394-41a7-a91c-a63a1176a8b1
Location
P T Bosley Senior Estates
4301 Warne Ave, St. Louis, MO
Phone: (314) 534-4700
4301 Warne Ave, St. Louis, MO
Phone: (314) 534-4700
Owner
Attn: Tramine Bradford
P T Bosley Senior Estates
4301 WARNE AVE, SAINT LOUIS, MO 63107
Phone: (314) 534-4700
Email: predd-brown@voail.org
P T Bosley Senior Estates
4301 WARNE AVE, SAINT LOUIS, MO 63107
Phone: (314) 534-4700
Email: predd-brown@voail.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.3 - Operating control devices | 210.1a | No | No | Replace missing stop switch in car operating panel | 2/8/2023 |
| A17.1-1996 : Elevators | 1.7 - Car door or gate | 204.4 | No | No | Adjust car door operator excessive force | 2/8/2023 |
| A17.1-1996 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 111.5 Restricted Opening of Hall/Car Doors | Yes | No | Door restricter not working | 2/24/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) | No | No | Need to include testing procedures in the MCP on or before 1/1/22 | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency phone not working | 12/21/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | Yes | On phase 1 recall door clos button does not work unable to test phase 2, ?Red tagged out of service | 12/21/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.1 Means of Communication (Red Tag) | No | No | Emergency phone still not working | 1/11/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state certificate in machine room | 1/9/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair phone in car. Reinspection required within 30 days | 3/26/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair Phone in the Car |