Inspection
Inspection Details
Equipment ID
14978
14978
Inspection Date
2/25/2021
2/25/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Tom Worsham
Tom Worsham
Relief Valve Pressure
280
280
Slide
Governor Rope Pull
Door Closing Force
17
17
External ID
b780ea23-e8b4-45e4-9c0c-11186ca8b9a5
b780ea23-e8b4-45e4-9c0c-11186ca8b9a5
Location
Best Western Plus
2621 E 5th St, Washington, MO
Phone: (636) 390-8877
2621 E 5th St, Washington, MO
Phone: (636) 390-8877
Owner
Narayandas LLC
2621 E 5TH ST, WASHINGTON, MO 63090-3856
2621 E 5TH ST, WASHINGTON, MO 63090-3856
Billing
Attn: Narayandas LLC
2621 E 5TH ST, WASHINGTON, MO 63090-3856
2621 E 5TH ST, WASHINGTON, MO 63090-3856
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a | Yes | No | Pit shall be kept clean and dry. | 3/6/2020 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit shall be kept clean and dry. | 3/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 2/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone does not work. | 3/30/2022 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display current operating certificate in machine room. | 3/25/2021 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed. Perform test on or before next annual inspection. | 3/25/2021 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | 2 way communication is not working, Re-inspection required | 2/28/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post Phase I instructions in lobby, near f/f switch. | 8/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide working pit light. | 8/14/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.1 Examination and Maintenance | No | No | Piston packing worn and leaking, repair as needed. | 8/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. | 8/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Determine if the sump pump works properly, if not replace. | 8/14/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 8/14/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Provide means to prevent ground water from entering the pit. To prevent rusting of pit equipment. | 8/14/2025 |