Inspection
Inspection Details
Equipment ID
7859
7859
Inspection Date
2/16/2021
2/16/2021
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Tim Crafton
Tim Crafton
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
510
510
Slide
Governor Rope Pull
Door Closing Force
15F/15R
15F/15R
External ID
0654537e-3ddb-48c4-b33d-6c2f07fcafe2
0654537e-3ddb-48c4-b33d-6c2f07fcafe2
Location
Sigma Chemical-Cherokee Bldg
165 CHEROKEE ST, SAINT LOUIS, MO
Phone: (314) 713-4729
165 CHEROKEE ST, SAINT LOUIS, MO
Phone: (314) 713-4729
Owner
Attn: Chuck Montgomery
Sigma Chemical
PO Box 14508, St. Louis, MO 63178
Phone: (314) 771-5765 Ext: 1513
Sigma Chemical
PO Box 14508, St. Louis, MO 63178
Phone: (314) 771-5765 Ext: 1513
Billing
Attn: Chuck Montgomery
Sigma Chemical
3300 S 2nd St, St. Louis, MO 63118
Phone: (314) 771-5765 Ext: 1513
Email: chuck.montgomery@milliporesigma.com
Sigma Chemical
3300 S 2nd St, St. Louis, MO 63118
Phone: (314) 771-5765 Ext: 1513
Email: chuck.montgomery@milliporesigma.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Cab walls separating from platform because of corrosion and abuse. Repair. | 6/25/2020 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Approx two cab wall sections separating from platform because of corrosion and abuse. Repair. | 6/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Car top light needs repair. | 6/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light needs repair. | 6/25/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Front and rear car gate astrigals. | 12/5/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 6/25/2020 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Approximately two cab wall sections separating from platform because of corrosion and abuse. Repair | 6/25/2020 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Repair car top light. | 6/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Repair pit light. | 6/25/2020 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)1 | No | No | Approximately two cab wall sections separating from platform because of corrosion and abuse. Repair. | 6/25/2020 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Car top light inoperable. | 6/25/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light switch fails to extinguish light when in "off" position. | 5/30/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | 8.6.5.16.5 OSV NOT SEALED TEST DUE BEFORE NEXT INSP DUE 3/1/2022 | 5/30/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is not sealed as noted in last inspection. Perform required testing, seal & tag within 90 days. Re-inspection required | 2/22/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working | 5/30/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room gate shall be self-closing. Repair existing closer on gate | 5/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency alarm shall work on auxiliary and normal power. Re-inspection required | 2/22/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing Phase I fire service sign by fire service keyswitch in hallway | 5/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Car gate reversing edges on both sides do not work. Repair same. Re-inspection required | 2/22/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light is not working | 5/30/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room gate shall be self closing, needs repair | 5/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency alarm shall work on auxiliary & normal power. Re-inspection required | 2/22/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Replace missing Phase I fire service sign by fire service keyswitch in hallway | 5/30/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Car gate reversing edges on both sides do not work, repair same. Re-inspection required | 2/22/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 5/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing hoistway/car door/gate pull straps, as needed. | 5/18/2023 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)2 | No | No | Hoistway door at Q3 floor has welded spacer. Welds have broken, spacer is bent, repair as needed. | 5/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Machine room/space has water dripping/splashing various spots, provide means to prevent. | 5/18/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide guard on bulbs in the elevator machine room, to prevent accidental contact or breakage. | 5/18/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide Code compliant fire extinguisher in the elevator machine room. | 5/18/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase I operations, no key. | 5/12/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase II operations, no key. | 5/12/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing phone door handle. | 5/18/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Provide existing pit light to work. | 5/18/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service Phase II shall work. Re-inspection required | 2/27/2024 |
| MO Minimum : Elevators | (C) - Car Enclosure: Freight | (C)5 | No | No | Repair or replace non working light in car. | 9/24/2024 |